Features
| Type | separated pleated cassette |
| Frame | galvanized steel |
| Filter media | glass fiber paper |
| Separators | corrugated aluminium |
| EN 779 Class | F6-F8 |
| Average arrestance | 98-99%(ASHRAE 52.1-1992) |
| MERV | MERV 12-15(ASHRAE 52.2-1999) |
| Protective Grids | galvanized steel mesh |
| Gasket | glass fiber loop |
| Final pressure drop | (recommender) 350Pa -(maximum)400Pa |
| Max. air flow rate | 125% of nominal air flow rate |
| Max. operating temperature | 260℃ |
| Max. relative humidity | 80% |
| Applications | fine particle filtration in ovens |
Specification
Type | Class | Dust Spot efficiency | Dimensions | Filtering surface (m2) | Rated air flow (m3/h) | Initial pressure drop(Pa) | ||
Length (mm) | Height (mm) | Depth (mm) | ||||||
HTG-65 | F6 | 60-65% | 595 | 595 | 292F | 11.0 | 3000 | 120 |
HTG-65 | F6 | 60-65% | 305 | 610 | 292 | 6.70 | 1700 | 120 |
HTG-65 | F6 | 60-65% | 610 | 610 | 292 | 13.5 | 3400 | 120 |
HTG-95 | F8 | 90-95% | 595 | 595 | 292F | 11.0 | 3000 | 140 |
HTG-95 | F8 | 90-95% | 305 | 610 | 292 | 6.70 | 1700 | 140 |
HTG-95 | F8 | 90-95% | 610 | 610 | 292 | 13.5 | 3400 | 140 |